ERRCS Annual Testing: What’s Required and How to Pass

An ERRCS isn’t done at acceptance. Fire codes require it to be tested every year and after any structural change — and fire marshals increasingly ask for the report at the annual inspection.

Makitech RF Engineering · Updated October 2026

What the code requires

CFC Section 510.6.1 requires ERCES testing annually and whenever structural changes occur, such as additions or remodels that could affect radio coverage. The test results go to the fire code official.1

What an annual test covers

  • Coverage test using the same grid method as acceptance testing, including critical areas.
  • Signal booster gain verified against the values recorded at acceptance.
  • Battery and power supply load test — at least one hour, extended if the batteries show signs of failure.
  • Active component checks of amplifiers, fiber units, and monitoring connections to the fire alarm system.

Source: CFC 510.6.1.1 Local standards often add items: Burbank adds quiescent noise, isolation, and leakage checks2, and San Diego requires semiannual visual inspections in addition to the annual test.3

Who can perform the test

Requirements vary by jurisdiction. Common requirements are an FCC General Radiotelephone Operator License (GROL), NICET In-Building Public Safety Communications certification, and manufacturer training on the installed equipment. Burbank, for example, requires NICET IB-PSC Level 3 for the person certifying the report.2

Common reasons systems fail

  • Tenant improvements that add walls, metal ceilings, or low-E glass and create new dead spots.
  • Donor signal changes when the public safety network adds or moves sites, or rebands channels.
  • Aged batteries that can no longer carry the load for the required duration.
  • Oscillation or gain drift from damaged antennas, cable faults, or reduced isolation.
  • Monitoring faults — trouble signals that no longer reach the fire alarm panel.

How to prepare

  1. Keep the acceptance report, grid map, and as-builts — the annual test uses the same grid.
  2. Record any construction since the last test.
  3. Check battery install dates against the manufacturer’s service life.
  4. Schedule the test ahead of the fire inspection so there’s time to correct failures.

Frequently asked questions

How often does an ERRCS need to be tested?

At least annually, and after structural changes that could affect coverage. Some jurisdictions also require semiannual visual inspections.

Can the original installer do the annual test?

Often yes, if they hold the qualifications your jurisdiction requires. Some AHJs require a third party for acceptance testing but allow qualified installers for annual tests.

What happens if the system fails the annual test?

The deficiencies must be corrected and re-tested, and the fire code official may require repairs within a set period. Burbank, for example, requires evaluation within 24 hours and repair within 5 working days for service-affecting failures.

References

  1. 2025 California Fire Code, Section 510. gocodebook.com
  2. City of Burbank Fire Department — ERRCS Regulations (effective Sept. 1, 2025). www.burbankca.gov
  3. San Diego Fire-Rescue Standard C-1 — Emergency Responder Communication Enhancement Systems. sandiego.gov

General information, not a substitute for your AHJ’s current requirements or a project-specific design. Local standards change; confirm with the fire code official.